7.5.3 Relay outputs, 10 and 11

Free programmable, dry contact relays for low voltages.
The two relays 10 and 11 can be configured for the emergency operation via the appropriate jumpers. During
emergency operation, the corresponding relay mode is permanently assigned to the two relays. In a CPU-
failure-mode of the system these relays are activated.
Wiring of relay 9, 10 and 11 (Relay-terminal card type Phoenix)
Terminal card
45
44
43
42
41
40
Relay 11
Relay 10
Fig. 43: Schematic wiring of the three dry contact relays 9, 10 and 11
Relay 9
Without CPU-failure-mode capability
Relay 10
Relays for low voltages without emergency operation mode or
selectable via jumper setting for >Emergency operation fire<
(refer to section "Emergency operation")
Relay 11
Relays for low voltages without emergency operation mode or
selectable via jumper setting for >Emergency operation trouble<
(refer to section "Emergency operation")
FB 798955.GB0 / 09.07
39
38
37
36
35
Relay 9
Extinguishing Control Computer 8010 – 19-Inch
Power supply and relay board
REL9
REL10
REL11
F2
F3
Emergency
operation
F4
Changeover contacts,
contact rating
max. 30 V DC / 2 A