8.1

Status functions

In case of an alarm event, the relay (AE) is activated relating to the status function pre selected in the customer
data. The relay can be triggered via several programmed OR logic operation status functions.
Common trouble
The programmed relay (AE) is activated if a common trouble is recognized.
Common disconnection
The programmed relay (AE) is activated if a common deactivation is recognized.
Common fire alarm
The programmed relay (AE) is activated if a common fire alarm is recognized.
Technical alarm
The programmed relay (AE) is activated if a technical alarm is recognized.
Extinguishing system triggered
The programmed output is activated if the extinguishing system is triggered.
Power fault without a delay
The programmed output is activated if a mains power failure is recognized.
Battery fault without a delay
The programmed output is directly activated if a battery failure is recognized.
Revision
The programmed output is activated if the revision mode is recognized.
PC Service (currently not supported)
The programmed output is directly activated if the PC Service is activated.
Preparation for service of the connected participants or the detector zones of the Extinguishing
Control Computer 8010 - series 3 with the programming software tools 8000.
Pressure relief flap #1, #2, #3
The programmed output is triggered to activate the pressure relief flap. Separate activation of up to three
pressure relief flaps is supported from system software version V3.02 in combination with the programming
software LKDE version V1.03R004 or higher.
Emergency Stop triggered
The programmed relay (AE) is triggered when an Emergency Stop button is pressed.
Power fault without a delay
The programmed output is activated if a mains power failure is recognized.
Battery fault, delayed
The programmed output is activated after a programmed delay if a battery failure is recognized.
Earth failure
The programmed relay (AE) is triggered when an failure, e.g. faulty insulation is recognized.