Extinguishing Control Computer 8010 – 19-Inch
12.3 Third-party detectors via Reset module to
LMST 8010 - 19-Inch series 2
Third-party detectors, e.g. the line-type smoke detector Fireray 50RV (Part No. 761315) or 100RV
(Part No. 761316) are connected to the Extinguishing Control Computer 8010 - 19-Inch series 2 via the Reset
module (Part No. 781332 / 781333).
Fit jumpers
6
5
K1
4
3
2
1
X2
Jumper X3, X5, X7, X8 fitted!
Jumper X4, X6 removed!
Connect cable shielding!
Observe wiring sequence!
For detailed informations and wirings refer to the technical manual of the Reset module.
74
X5
X6
X7
X8
X3
X4
Reset module
X1
black
5
red
4
blue
2
white
7
yellow
3
6
green
Plug w ith cable
(lengh t appro x. 50cm )
6
5
4
3
2
1
R
A LA R M
1K
10K
R
E ND
Extinguishing Control Computer
standard detector zone
Detector zone input
Gn -
Gn +
Extinguishing Control Computer
external power supply or
DC/DC converter
(Min. 1A switch current)
0V
+24V
FB 798955.GB0 / 09.07