Bosch Rexroth IndraDrive MPH-02 Functional Description page 640

Firmware for drive controllers
Table of Contents

Advertisement

10-58
Handling, Diagnostic and Service Functions
Pertinent Parameters
• P-0-0480, Patch function 1, source pointer
• P-0-0481, Patch function 1, attribute
• P-0-0482, Patch function 1, bit mask
• P-0-0483, Patch function 1, exponent
• P-0-0485, Patch function 1, display
• P-0-0486, Patch function 2, source pointer
• P-0-0487, Patch function 2, attribute
• P-0-0488, Patch function 2, bit mask
• P-0-0489, Patch function 2, exponent
• P-0-0491, Patch function 2, display
Functional Description
(Displaying Internal Storage Locations/Signals)
Read Access
The patch function allows transforming any storage location into a data
object that can be read via the master communication. To do this, a
storage location is preset via the parameters P-0-0480, Patch function 1,
source pointer and P-0-0486, Patch function 2, source pointer. The
access to this address is configured via bits 0 to 2 of the parameters
P-0-0481, Patch function 1, attribute and P—0487, Patch function 2,
attribute. INT4 reads a 4-byte integer value starting from the source
pointer, INT2/INT1 read 2 bytes or 1 byte accordingly. FLOAT8 reads an
8-byte floating-point value (DOUBLE), FLOAT4 reads 4 bytes accordingly
(FLOAT).
Due to the processor architecture the possible memory accesses are
subject to certain restrictions. A 4-byte access, for example, is only
allowed for storage locations the address of which can be divided by 4.
The table below contains a complete overview of the allowed and
prohibited memory accesses.
Note:
If you want to change the access mode via bits 0 to 2 of the
patch attribute parameters (P-0-0481/P-0-0487), this is only
possible if the patch source pointer that has just been set
(P-0-0480/P-0-0486) allows the new access mode (see table).
possible access to source addresses that ...
can be divided
by 4
access as...
(DWORD-aligned)
á
INT4
á
INT2
á
INT1
á
FLOAT8
á
FLOAT4
á:
access allowed
X:
access prohibited
Fig. 10-24: Possible access modes
The desired display format is set via bits 4 to 7 of the patch attribute
parameters (P-0-0481/P-0-0487). This allows interpreting the value read
as a decimal number with or without sign, as a hexadecimal number or as
MPH-02, MPB-02, MPD-02
can be divided by 2,
do not have any
but not by 4
particular alignment
(WORD-aligned)
(BYTE-aligned)
X
á
á
X
X
DOK-INDRV*-MP*-02VRS**-FK01-EN-P
X
X
á
X
X