Idn Lists Of Parameters - Bosch Rexroth IndraDrive MPH-02 Functional Description

Firmware for drive controllers
Table of Contents

Advertisement

MPH-02, MPB-02, MPD-02

IDN Lists of Parameters

DOK-INDRV*-MP*-02VRS**-FK01-EN-P
Handling, Diagnostic and Service Functions
Respective diagnostic command message:
• C0400 Switching to parameter mode
Respective diagnostic messages in the case of possible command errors:
• C0402 Only allowed without master
Note:
The drive returns to the operating mode by a successive start
of the commands S-0-0127, C0100 Communication phase 3
transition check and S-0-0128, C0200 Communication
phase 4 transition check!
When reading and writing individual parameters via the control master or
DriveTop (without command), the following error messages can possibly
occur:
• F2100 Flash defective
• F2101 It was impossible to address MMC
• F2102 It was impossible to address I2C memory
• F2103 It was impossible to address EnDat memory
Some of the parameters stored in the drive contain, as their operating
data (parameter value), a list of IDNs of drive parameters. These so-
called IDN lists enable the master or a commissioning software to handle
drive parameters in a specific way.
S-0-0017, IDN-list of all operation data
The parameter S-0-0017, IDN-list of all operation data contains the
IDNs of all parameters available in the drive.
S-0-0192, IDN-list of backup operation data
The parameter S-0-0192, IDN-list of backup operation data contains
the IDNs of all parameters that are stored in the non-volatile memory
[MultiMediaCard (MMC) or flash memory]. These parameters are required
for correct operation of the drive. With the master or a commissioning
software it is possible to use this IDN list for making a backup copy of the
drive parameters.
S-0-0021, IDN list of invalid operating data for
communication phase 2
In parameter S-0-0021, IDN list of invalid operating data for
communication phase 2 the IDNs of those parameters are automatically
entered that the drive software detects as being invalid when executing
the S-0-0127, C0100 Communication phase 3 transition check
command.
10-11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rexroth indradrive mpb-02Rexroth indradrive mpd-02

Table of Contents