Restrictions
A pulse generator with a zero signal is required. When using a pulse generator without a zero signal, produce a zero signal
using an external signal.
Precautions during the operation
• If the distance set in "[Pr.50] Setting for the movement amount after near-point dog ON" is shorter than the deceleration
distance from "[Pr.46] OPR speed" to deceleration stop, a Count method movement amount fault (Error code: 1944H)
occurs and the operation does not start.
• If the speed is changed to a speed faster than the speed set in [Pr.46] OPR speed using the speed change function
(Page 241 Speed change function ) during a machine OPR operation, the distance required for deceleration stop may
not be assured depending on the setting of "[Pr.50] Setting for the movement amount after near-point dog ON".In this case,
Count method movement amount fault (Error code: 1944H) occurs and the machine OPR is stopped.
• The following shows the operation performed when the machine OPR is started while the near-point dog is on.
(4)
(3)
ON
Near-point dog
OFF
Zero signal
• The near-point dog must be turned off at a sufficient distance from the OP. There is no harm in operation even if the near-
point dog is turned off during a machine OPR. However, ensuring a sufficient distance from the OP is recommended for the
following reasons when the near-point dog is turned off.
(1) If the workpiece is at a point where the near-point dog is still ON when the machine OPR is completed, another machine OPR can be implemented from that
point even though the OPR complete flag ([Md.31] Status: b4) is ON.
(2) If the workpiece is at a point where the near-point dog is OFF when the machine OPR is completed and another OPR is implemented, the workpiece travels
at the OPR speed until it reaches a limit switch. This causes Hardware stroke limit (+)/Hardware stroke limit (-) (Error code: 1905H/1907H). If a sufficient
distance cannot be ensured for Near-point dog signal to be turned on, use the OPR retry function. When the OPR retry function is used, a retry operation
can be performed using limit switches.
• When the machine OPR has been stopped by a stop signal, perform the machine OPR again. If the restart command is
turned ON after the stop by a stop signal, OPR restart not possible (Error code: 1946H) occurs.
[Pr.50] Setting for the movement
amount after near-point dog ON
(1)
(5)
(2)
[Operation when the machine OPR is started from a point where the near-point
dog is on]
(1) A machine OPR is started.
(2) The machine moves at the OPR speed in the direction reverse to the
specified OPR direction.
(3) The deceleration processing is performed according to the setting of [Pr.39]
Stop group 3 sudden stop selection when the OFF state of the near-point
dog is detected.
(4) After the machine stops, the machine OPR is performed in the specified
OPR direction.
(5) The machine OPR is completed after the deviation counter clear output is
provided on the detection of the first zero signal after the workpiece travels
for the movement amount set in [Pr.50] Setting for the movement amount
after near-point dog ON from the point where the ON state of the near-point
dog is detected.
8 OPR CONTROL
87
8.2 Machine OPR
8