Mitsubishi Electric MELSEC iQ-F Series FX5 User Manual page 456

Positioning control - intelligent function module
Hide thumbs Also See for MELSEC iQ-F Series FX5:
Table of Contents

Advertisement

[Cd.2] Module data initialization request
Set this area to initialize module parameters and module extension parameters (positioning data and block start data) in the
buffer memory and setting values in the module extension parameter file to their factory default settings.
Module data initialization request
Not requested
Requested
• After the data is initialized, 0 is automatically stored. Storing 0 indicates the completion of the initialization.
• After the data is initialized, turn on the system again, or reset the CPU module.
• For details on the module data initialization function, refer to the following.
Page 301 Module Data Initialization Function
■Buffer memory address
The following table shows the buffer memory address of this area.
Buffer memory name
[Cd.2] Module data initialization request
■Default value
The default value is 0.
[Cd.41] Deceleration start flag valid
Set whether to validate [Md.48] Deceleration start flag.
Deceleration start flag valid
Deceleration start flag invalid
Deceleration start flag valid
■Buffer memory address
The following table shows the buffer memory address of this area.
Buffer memory name
[Cd.41] Deceleration start flag valid
■Default value
The default value is 0: Deceleration start flag invalid.
[Cd.42] Stop command processing for deceleration stop selection
Set the stop command processing for deceleration stop function (deceleration curve re-processing or deceleration curve
continuation).
Stop command processing for deceleration stop selection
Deceleration curve re-processing
Deceleration curve continuation
■Buffer memory address
The following table shows the buffer memory address of this area.
Buffer memory name
[Cd.42] Stop command processing for deceleration stop selection
■Default value
The default value is 0: Deceleration curve re-processing.
17 DATA USED FOR POSITIONING CONTROL
454
17.8 Control Data
Setting value
0
1
Common for axes 1 and 2
1901
Setting value
0
1
Common for axes 1 and 2
1905
Setting value
0
1
Common for axes 1 and 2
1907

Advertisement