General Data - Siemens SINAMICS G150 Operating Instructions Manual

Converter cabinet units 75 kw to 1500 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Technical specifications

12.2 General data

12.2
General data
Table 12- 1
General technical data
Electrical data
Line system configurations
Line frequency
Output frequency
Power factor
- Fundamental mode
- Total
Converter efficiency
Switching at input
Overvoltage category
Mechanical data
Degree of protection
Class of protection
Cooling method
Sound pressure level L
pA
(1 m)
Touch protection
Cabinet system
Paint finish
Compliance with standards
Standards
CE mark
RI suppression
Ambient conditions
Ambient temperature
Humidity range
2)
(non-condensing)
corresponds to class
Environmental class/harmful
chemical substances
2)
Organic/biological influences
2)
Degree of pollution
Installation altitude
580
Grounded TN/TT systems or ungrounded IT systems (a grounded phase conductor is not
permissible in 690 V line supplies)
47 ... 63 Hz
0 ... 300 Hz
≥ 0,96
0,75 ... 0,93
> 98 %
Once every 3 minutes
III according to EN 61800-5-1
IP20 (higher degrees of protection up to IP54 optional)
I acc. to EN 61800-5-1
Forced air cooling AF to EN 60146
at 50 Hz line frequency
≤ 72 dB(A) (single units) / ≤ 75 dB(A) (units that are connected in parallel)
at 60 Hz line frequency
≤ 75 dB(A) (single units) / ≤ 78 dB(A) (units that are connected in parallel)
EN 50274 and BGV A3 when used as intended
Rittal TS 8, doors with double-barb lock, three-section base plates for cable entry
RAL 7035 (indoor requirements)
EN 60146-1, EN 61800-2, EN 61800-3, EN 61800-5-1, EN 60204-1, EN 60529
To EMC directive No. 2004/108/EC and low-voltage directive No. 2006/95/EC
In accordance with the EMC product standard for variable-speed drives EN 61800-3,
"second environment".
Application in "first environment" possible with line filters (option L00)
Storage
-25 ... +55 °C
5 to 95 %
1K4 to EN 60721-3-1
1C2 to EN 60721-3-1
1B1 to EN 60721-3-1
2 according to EN 61800-5-1
Up to 2000 m above sea level without derating,
> 2000 m above sea level with derating (see "Derating data")
Transport
-25 ... +70°C
–40 °C
as of
for 24 hours
5 ... 95 % at 40 °C
2K3 to EN 60721-3-2
2C2 to EN 60721-3-2
2B1 to EN 60721-3-2
Operating Instructions, 03/2012, A5E03263466A
2)
.
1)
Operation
0
... +40 °C
up to +50 °C with derating
95 %
5 ...
3K3 to EN 60721-3-3
3C2 to EN 60721-3-3
3B1 to EN 60721-3-3
Converter cabinet units