Electrical installation
4.11 Other connections
CAUTION
When a dV/dt filter plus Voltage Peak Limiter is used, the drive must not be operated
without a connected motor, otherwise the filter can be destroyed.
Note
It is permissible to set pulse frequencies in the range between the rated pulse frequency and
the relevant maximum pulse frequency when a dV/dt filter plus Voltage Peak Limiter is used.
When so doing, take into account the "Current derating as a function of the pulse frequency;
see Technical data.
Table 4- 34
Max. pulse frequency when a dV/dt filter plus Voltage Peak Limiter is used in units with a rated pulse
frequency of 2 kHz
Order no.
6SL3710-...
1GE32-1AAx
1GE32-6AAx
1GE33-1AAx
1GE33-8AAx
1GE35-0AAx
Table 4- 35
Max. pulse frequency when a dV/dt filter plus Voltage Peak Limiter is used in units with a rated pulse
frequency of 1.25 kHz
Order no.
6SL3710-...
1GE36-1AAx
1GE37-5AAx
1GE38-4AAx
1GE41-0AAx
2GE41-1AAx
2GE41-4AAx
2GE41-6AAx
124
Unit rating [kW]
Output current for a
pulse frequency of 2 kHz [A]
Supply voltage 380 ... 480 V AC
110
132
160
200
250
Unit rating [kW]
Output current for a
pulse frequency of 1.25 kHz
Supply voltage 380 ... 480 V AC
315
400
450
560
630
710
900
Max. pulse frequency when a dV/dt filter
plus Voltage Peak Limiter is used
210
260
310
380
490
Max. pulse frequency when a dV/dt filter
plus Voltage Peak Limiter is used
[A]
605
745
840
985
1120
1380
1580
Operating Instructions, 03/2012, A5E03263466A
4 kHz
4 kHz
4 kHz
4 kHz
4 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
Converter cabinet units