Functions, Monitoring, and Protective Functions
9.2 Drive Functions
6. After entering the frequency in p0113, parameter p0009 on the Control Unit must be set
7. The Control Unit re-initializes. After booting, the pulse frequencies recommended in
9.2.10.4

Maximum output frequency achieved by increasing the pulse frequency

By multiplying the basis pulse frequency (with integers), the following output frequencies can
be achieved (taking into account the derating factors):
Table 9- 5
The maximum output frequency is limited to 300 Hz due to the closed-loop control.
1)
9.2.10.5

Parameters

• p0009
• p0112
• p0113
• p0115
• p1800
454
to 0 "Ready" again.
r0114[i] (i = 1, 2, ...) can be entered in parameter p1800 "Pulse frequency" of the DO
VECTOR.
NOTICE
The pulse frequency entered in p1800 must correspond precisely to the value given in
r0114[i]; otherwise, the entry will be rejected.
Maximum output frequency achieved by increasing the pulse frequency
Pulse frequency
[kHz]
1.25
2
2.5
4
5
Device commissioning parameter filter
Sampling times pre-setting p0115
Selects the minimum pulse frequency
Sampling times
Pulse frequency
Maximum output frequency
[Hz]
100
160
200
300
1)
300
1)
Operating Instructions, 03/2012, A5E03263466A
Converter cabinet units