Advertisement

Commissioning
5.3 Procedure for commissioning via STARTER
Results of the previous steps
● You have created a drive unit project offline using STARTER.
● You have saved the project data to the hard disk on your PC.
● You have transferred the project data to the drive unit.
● You have saved your project data to the CompactFlash card so that it is backed up in the
Note
The STARTER commissioning tool supports complex drive system operations.
If you are confronted with any system conditions in online mode that are beyond your
control, you are advised to delete the drive project from the project navigator and carefully
create a new project in STARTER using the appropriate configuration data for your
application.
5.3.5

Commissioning with STARTER via Ethernet

Description
The Control Unit can be commissioned using PG/PC via the integrated Ethernet Interface.
This interface is provided for commissioning purposes only and cannot be used to control the
drive in operation.
Preconditions
● STARTER from version 4.1.5 or higher
● Control Unit CU320-2 DP from device version "C", CU320-2 PN Control Unit
STARTER via Ethernet (example)
Figure 5-31
234
event of a power failure.
STARTER via Ethernet (example)
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A