Functions, Monitoring, and Protective Functions
9.2 Drive Functions
Faults without automatic restart (p1206)
Up to 10 fault numbers for which the automatic restart should not be effective can be
selected via p1206[0...9].
The parameter is only effective if p1210 = 6 and p1210 = 16.
Parameter
• p1206[0...9]
• p1210
• p1211
• p1212
• p1213
• r1214
Settings
To prevent the motor from switching to phase opposition when the drive is being restarted,
there is a delay while the motor demagnetizes (t = 2.3 x motor magnetization time constant).
Once this time has elapsed, the inverter is enabled and the motor is supplied with power.
438
Faults without automatic restart
Automatic restart mode
Automatic restart, start attempts
Automatic restart, delay time start attempts
Automatic restart monitoring time
Automatic restart status
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A