Siemens SINAMICS G150 Operating Instructions Manual page 518

Converter cabinet units 75 kw to 1500 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Diagnosis / faults and alarms
10.2 Diagnosis
Table 10- 2
Description of the LEDs on the CU320-2 PN control unit
LED
Color
RDY (READY)
---
Green
Red
Red/green
Orange
Green/oran
ge or
red/orange
PN
---
PROFIdrive cyclic
operation
Green
Red
OPT
---
(OPTION)
Green
Red
RDY and DP
Red
RDY and OPT
Orange
516
State
Description
OFF
The electronic power supply is missing or lies outside the
permissible tolerance range.
Continuous light
The component is ready for operation and cyclic DRIVE-CLiQ
communication is taking place.
The control unit is waiting for initial commissioning.
0.5 Hz flashing
Commissioning/reset
light
2 Hz flashing light
Writing to CompactFlash card.
2 Hz flashing light
General faults
0.5 Hz flashing
Control Unit is ready for operation.
light
However, there are no software licenses.
0.5 Hz flashing
Firmware update in progress for the connected DRIVE-CLiQ
light
components.
2 Hz flashing light
Firmware update of components has been completed. Wait for
POWER ON of the respective component.
2 Hz flashing light
Component detection via LED is activated (p0124[0]).
Note:
The two options depend on the LED status when component
detection is activated via p0124[0] = 1.
OFF
Cyclic communication is not (yet) running.
Note:
PROFIdrive is ready for communication when the control unit is
ready for operation (see RDY LED).
Continuous light
Cyclic communication is taking place.
0.5 Hz flashing
Cyclic communication is still not completely running.
light
Possible causes:
- The controller is not transferring any setpoints.
- For isochronous operation, either none or a faulty Global Control
(GC) has been transferred from the controller.
- "Shared Device" has been selected (p8929 = 2) and only one
controller connected.
0.5 Hz flashing
Bus error, incorrect parameter assignment/configuration
light
2 Hz flashing light
Cyclic bus communication has been interrupted or could not be
established.
OFF
Electronic power supply outside permissible tolerance range.
The component is not ready for operation.
The option board is missing or an associated drive object has not
been created.
Continuous light
Option board is ready.
0.5 Hz flashing
Depends on the option board used.
light
2 Hz flashing light
This component has at least one fault.
The option board is not ready (e.g., after switching on).
2 Hz flashing light
Bus error - communication has been interrupted.
0.5 Hz flashing
Firmware update in progress for connected option board CBE20.
light
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A

Advertisement

Table of Contents
loading

Table of Contents