Settings: MENU – Commissioning/Service – AOP Settings – Control Settings
Save LOCAL mode (factory setting: yes)
● Yes: The "LOCAL" or "REMOTE" operating mode is saved when the power supply is
● No: "LOCAL" or "REMOTE" operating mode is not saved. "REMOTE" is active when the
OFF in REMOTE (factory setting: no)
● Yes: The OFF key functions in REMOTE mode even if the drive is being controlled by
● No: The OFF key only functions in LOCAL mode.
LOCAL/REMOTE also during operation (factory setting: No)
● Yes: You can switch between LOCAL and REMOTE when the drive is switched on (motor
● No: Before the system switches to LOCAL, a check is carried out to determine whether
6.6.7.2

ON key / OFF key

ON key: always active in LOCAL when the operator input inhibit is deactivated.
OFF key: in the factory setting, acts as OFF1 = ramp-down at the deceleration ramp (p1121);
when n = 0: voltage disconnection (only if a main contactor is installed)
The OFF key is effective in the LOCAL mode and when the "OFF in REMOTE" function is
active.
Settings: Menu – Commissioning / Service – AOP Settings – Control Settings
Red OFF key acts as: (factory setting: OFF1)
● OFF1: Ramp-down on the deceleration ramp (p1121)
● OFF2: Immediate pulse block, motor coasts to a standstill
● OFF3: Ramp-down on the emergency stop ramp (p1135)
6.6.7.3

Switching between clockwise and counter-clockwise rotation

Settings: MENU – Commissioning/Service – AOP settings – Control settings
Switching between CCW/CW (factory setting: no)
● Yes: Switching between CW/CCW rotation by means of the CW/CCW key possible in
● No: The CW/CCW key has no effect in LOCAL mode
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
switched off and restored when the power supply is switched back on.
supply voltage is switched back on.
external sources (PROFIBUS, customer terminal strip, NAMUR terminal strip).
WARNING This function is not an EMERGENCY STOP function!
is running).
the drive is in the operational status. If so, the system does not switch to LOCAL and
outputs the message "Local not possible". Before the system switches to REMOTE, the
drive is switched off and the setpoint is set to 0.
LOCAL mode
6.6 Control via the operator panel
Operation
303