Electrical installation
4.11 Other connections
Commissioning
When commissioning using the STARTER or AOP30, the sine-wave filter must be activated
by means of appropriate selection screenforms or dialog boxes (p0230 = 3), see section
"Commissioning".
The following parameters are changed automatically during commissioning.
Table 4- 38
Parameter
Note
When the factory settings are restored, parameter p0230 is reset.
The parameter must be reset if the system is commissioned again.
128
Parameter settings for sine-wave filters with SINAMICS G150
p0230
Drive filter type, motor side
p0233
Power unit motor reactor
p0234
Power unit sine-wave filter
capacitance
p0290
Power unit overload response
p1082
Maximum speed
p1800
Pulse frequency
p1802
Modulator mode
p1909
Motor data identification, control word Rs measurement only
Name
3: Siemens sine-wave filter
Filter inductance
Filter capacitance
Disable pulse frequency reduction
Fmax filter / pole pair number
Nominal pulse frequency of the filter (see
previous table)
Space-vector modulation without
overmodulation
Setting
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A