Functions, Monitoring, and Protective Functions
9.2 Drive Functions
9.2.6.3

Parameters

• p0352
• p1200
• p1202
• p1203
• r1204
• r1205
Note
For p1200 = 1, 2, 3, the following applies: Search in both directions, start only in the setpoint
direction.
For p1200 = 4, 5, 6, the following applies: Search only in the setpoint direction.
442
Cable resistance
Flying restart operating mode
• 0: Flying restart inactive
• 1: Flying restart always active (start in setpoint direction)
• 2: Flying restart active after On, error, OFF2 (start in setpoint direction)
• 3: Flying restart active after error, OFF2 (start in setpoint direction)
• 4: Flying restart always active (start only in setpoint direction)
• 5: Flying restart active after On, error, OFF2 (start only in setpoint
direction)
• 6: Flying restart active after error, OFF2 (start only in setpoint direction)
Flying restart search current
Flying restart search speed factor
Flying restart, V/f control status
Flying restart, vector control status
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A