Field
Format
Number of values
Error values
Values
Error values in DPV1 parameter responses
Table 6- 20
Error values in DPV1 parameter responses
Error
value
0x00
Illegal parameter number.
0x01
Parameter value cannot be changed.
0x02
Lower or upper value limit exceeded.
0x03
Invalid subindex.
0x04
No array.
0x05
Wrong data type.
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
Data type
Unsigned8
The format and number specify the adjoining space containing values in the telegram.
For write access, it is preferable to specify data types according to the PROFIdrive profile.
Bytes, words and double words are also possible as a substitute.
Unsigned8
Specifies the number of subsequent values.
Unsigned16
The error values in the event of a negative response.
If the values make up an odd number of bytes, a zero byte is attached. This ensures the
integrity of the word structure of the telegram.
Unsigned16
The values of the parameter for read or write access.
If the values make up an odd number of bytes, a zero byte is attached. This ensures the
integrity of the word structure of the telegram.
Meaning
6.7 Communication according to PROFIdrive
Values
0x02
0x03
0x04
0x05
0x06
0x07
0x08
Other values
0x40
0x41
0x42
0x43
0x44
0x00 ... 0xEA
0x0000 ... 0x00FF
0x0000 ... 0x00FF
Comment
Access to a parameter that does not exist.
Modification access to a parameter value that cannot be
changed.
Modification access with value outside value limits.
Access to a subindex that does not exist.
Access with subindex to an unindexed parameter.
Modification access with a value that does not match the
data type of the parameter.
Comment
Data type integer8
Data type integer16
Data type integer32
Data type unsigned8
Data type unsigned16
Data type unsigned32
Data type floating point
See PROFIdrive profile V3.1
Zero (without values as a positive
subresponse of a write request)
Byte
Word
Double word
Error
No. 0 ... 234
Limited by DPV1 telegram length
Meaning of error values
--> see following table
Subindex
Subindex
Subindex
Operation
Additional
info