Timeout Monitoring; Operator Input Inhibit / Parameterization Inhibit - Siemens SINAMICS G150 Operating Instructions Manual

Converter cabinet units 75 kw to 1500 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Operation
6.6 Control via the operator panel
Settings: MENU – Commissioning/Service – AOP Settings – Control Settings
Acknowledge error from the AOP (factory setting: yes)
● Yes: Errors can be acknowledged via the AOP.
● No: Errors cannot be acknowledged via the AOP.
Settings: MENU – Commissioning/Service – AOP settings – Control settings
CDS changeover via AOP (factory setting: No)
● Yes: In the LOCAL mode, in the operating screen form the active CDS can the changed
● No: In the LOCAL mode, in the operating screen form the active CDS cannot be changed
6.6.7.7

Timeout monitoring

In "LOCAL" mode or if "OFF in REMOTE" is active, the drive is shut down in an adjustable
time if the data cable between the AOP and drive is disconnected (factory setting 3000 ms).
6.6.7.8

Operator input inhibit / parameterization inhibit

To prevent users from accidentally actuating the control keys and changing parameters, you
can activate an operator input / parameters disable using a key pushbutton. Two key icons
appear in the top right of the display when these inhibit functions are enabled.
Table 6- 10
Inhibit type
No inhibit
Operator input inhibit
Parameters disable
Operator input inhibit + parameters disable
306
by one. This is helpful, if operation via an AOP would not be possible due to the fact that
a standard telegram is active.
When CDS0 or 2 is active, "CDS+1" switches to CDS1 or CDS3.
When CDS1 or 3 is active, "CDS-1" switches to CDS0 or CDS2.
by one.
Display of operator input/parameters disable
Online operation
Operating Instructions, 03/2012, A5E03263466A
Offline operation
Converter cabinet units