Siemens SINAMICS G150 Operating Instructions Manual page 127

Converter cabinet units 75 kw to 1500 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Order no.
6SL3710-...
1GF31-8AAx
1GF32-2AAx
1GF32-6AAx
1GF33-3AAx
1GF34-1AAx
1GF34-7AAx
1GF35-8AAx
1GF37-4AAx
1GF38-1AAx
2GF38-6AAx
2GF41-1AAx
2GF41-4AAx
1GH28-5AAx
1GH31-0AAx
1GH31-2AAx
1GH31-5AAx
1GH31-8AAx
1GH32-2AAx
1GH32-6AAx
1GH33-3AAx
1GH34-1AAx
1GH34-7aAx
1GH35-8AAx
1GH37-4AAx
1GH38-1aAx
2GH41-1AAx
2GH41-4AAx
2GH41-4AAx
Commissioning
During commissioning, the dv/dt filter plus Voltage Peak Limiter must be logged on using
STARTER or the AOP30 operator panel (p0230 = 2).
Note
When the factory settings are restored, parameter p0230 is reset.
The parameter must be reset if the system is commissioned again.
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
Unit rating [kW]
Output current for a
pulse frequency of 1.25 kHz
Supply voltage 500 ... 600 V AC
110
132
160
200
250
315
400
500
560
630
710
1000
Supply voltage 660 ... 690 V AC
75
90
110
132
160
200
250
315
400
450
560
710
800
1000
1350
1500
Max. pulse frequency when a dV/dt filter
plus Voltage Peak Limiter is used
[A]
175
215
260
330
410
465
575
735
810
860
1070
1360
85
100
120
150
175
215
260
330
410
465
575
735
810
1070
1360
1500
Electrical installation
4.11 Other connections
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz