Mitsubishi Electric FR-A700 Instruction Manual page 695

Frequency inverter
Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Parameter
Wiring Length
Pull up/down resistance
Load current (for reference)
Tab. 6-176: resistance values for p ull up and pull down resistances
Stray capacitances of the wiring greately differ according to the cable type and cable laying, the
above cable length is not a guaranteed value.
When using a pull up resistance, check the permissible power of the resistor and permissible
load current of output transistor and use them within a permissible range.
NOTES
When pulse train input is selected, a function assigned to terminal JOG using Pr. 185 JOG
terminal function selection is made invalid.
When Pr. 419 Position command source selection = "2" (conditional position pulse train
command by inverter pulse train input), JOG terminal serves as conditional position pulse
train terminal regardless of the Pr. 291.
Pulse train input specifications
Item
Available pulse method
H input level
L input level
Maximum input pulse rate
Minimum input pulse width
Input resistance/load current
Maximum wiring length
(reference value)
Detection resolution
Tab. 6-177: Pulse train input specification
The wiring length of complementary output depends on the output wiring specifications of
complementary output device. Stray capacitances of the wiring greatly differ according to
the cable type and cable laying, the maximum cable length is not a guaranteed value.
NOTE
When pulse train input is selected, a function assigned to terminal JOG using Pr. 185 "JOG
terminal function selection" is made invalid.
FR-A700 EC
Less than 10m
Not necessary
10mA
Open collector output system
Complemenraty output system
10 to 50 m
1kΩ
35mA
Specifications
Open collector output
Complimentary output (power supply voltage 24V)
20V or more (voltage between JOG-SD)
5V or less (voltage between JOG-SD)
100kpps
2.5µs
2kΩ (typ.)/10mA (typ.)
10m (0.75 mm²/ twisted pair)
100m (output resistance 50Ω)
1/3750
Special operation
50 to 100 m
470Ω
65mA
6 - 515

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a740 ecFr-a700 ec