Parameter
6.14.9

Remote output function (REM, Pr. 495 to Pr. 497)

You can utilize the on/off of the inverter's output signals instead of the remote output terminal of
the programmable logic controller.
Pr.
Name
No.
Remote output
495
selection
496
Remote output data 1
497
Remote output data 2
The above parameters allow its setting to be changed during operation in any operation
mode even if "0" (initial value) is set in Pr. 77 "Parameter write selection".
The output terminal can be turned on/off depending on the Pr. 496 or Pr. 497 setting. The remote
output selection can be controlled on/off by computer link communication from the PU connector
or RS-485 port or by communication from the communication option.
Set "96" (source logic) or "196" (sink logic) to any of Pr. 190 to Pr. 196 "Output terminal function
selection", and assign the remote output (REM) signal to the terminal used for remote output.
FR-A700 EC
Initial
Setting
Description
Value
Range
0
Remote output data clear at powering off
Remote output data retention even at
1
powering off
0
10
Remote output data clear at powering off
Remote output data retention even at
11
powering off
0
0–4095
Refer to Fig. 6-141
0
0–4095
Function assignment of external terminals
Parameters referred to
190–196
Output terminal
function selection
Refer to
Section
6.14.5
6 - 315