Use The Digital Dial Like A Potentiometer To Perform Operation - Mitsubishi Electric FR-A700 Instruction Manual

Frequency inverter
Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

PU operation mode
5.2.2

Use the digital dial like a potentiometer to perform operation

● Set "1" (setting dial potentiometer mode) in Pr. 161 "Frequency setting/key lock operation
selection".
Example
Change the frequency from 0Hz to 50Hz during operation.
Fig. 5-18: Use the digital dial like a potentiometer to perform operation
NOTES
If flickering "50.00" turns to "0.0", the Pr. 161 "Frequency setting/key lock operation selec-
tion" setting may not be "1".
Independently of whether the inverter is running or at a stop, the frequency can be set by
merely turning the digital dial.
5 - 42
Operation
Screen at powering on
The monitor display appears.
Press the PU/EXT key to choose the PU
operation mode.
Change Pr. 161 to the setting value of "1".
(Refer to section 4.3.7 for change of the setting.)
Press the FWD or REV key to start the inverter.
Turn the digital dial until "50.00"appears.
The flickering frequency is the set frequency. You
don't need to press the SET key.
Basic settings
Display
PU indication is lit.
The frequency flickers for about 5s.
I001071E

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a740 ecFr-a700 ec

Table of Contents