Operation Setting At Alarm Occurrence; Retry Function - Mitsubishi Electric FR-A700 Instruction Manual

Frequency inverter
Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Parameter
6.17

Operation setting at alarm occurrence

Purpose
Recover by retry operation at alarm
occurrence
Output alarm code from terminal
Do not input/output phase failure
alarm
The motor is decelerated to stop at
motor thermal activation
6.17.1

Retry function

If an alarm occurs, the inverter resets itself automatically to restart. You can also select the alarm
description for a retry.
When automatic restart after instantaneous power failure is selected (Pr. 57 "Restart coasting
time" ≠ 9999), restart operation is performed at retry operation as at an instantaneous power fail-
ure. (Refer to section 6.16.1 for the restart function.)
Pr.
Name
No.
65
Retry selection
Number of retries at
67
alarm occurrence
68
Retry waiting time
69
Retry count display erase
FR-A700 EC
Parameters that must be set
Retry operation
Alarm code output function
Input/output phase failure protection
selection
Fault definition
Initial
Setting
Description
Value
Range
0
0–5
An alarm for retry can be selected.
0
No retry function
Set the number of retries at alarm occur-
1–10
rence. An alarm output is not provided
during retry operation.
0
Set the number of retries at alarm occur-
rence.
(The setting value of minus 100 is the
101–110
number of retries.)
An alarm output is provided during retry
operation.
Set the waiting time from when an
50Hz
0–10s
inverter alarm occurs until a retry is
made.
Clear the number of restarts succeeded
0
by retry.
Operation setting at alarm occurrence
Pr. 65,
Pr. 67–Pr. 69
Pr. 76
Pr. 251, Pr. 872 6.17.3
Pr. 875
Parameters referred to
57
Restart coasting
time
Refer to
section
6.17.1
6.17.2
6.17.6
Refer to
Section
6.16.1
6 - 351