Wiring
Connection to the conductors
When wiring the inverter main circuit conductor of the 05470 or more, tighten a nut from the right
side of the conductor. When wiring two wires, place wires on both sides of the conductor. (Refer
to the drawing below.) For wiring, use bolts (nuts) provided with the inverter.
Wiring cover
The frequency inverters FR-A740-00470 and 00620 are equipped with a combed shaped wiring
cover. For the hook of the wiring cover, cut off the necessary parts using a pair of long-nose
pliers etc.
Fig. 3-5: Combed shaped wiring cover
NOTE
Cut off the same numbers of lugs as wires. If you cut off unnecessary parts and no wires are
connected, the protective structure (JEM 1030) of the inverter becomes open type (IP00).
FR-A700 EC
Main circuit connection
Fig. 3-4:
Connection to the conductors
I001346E
I000999E
3 - 11