Wiring
3.2

Terminal connection diagram

Source Logic
*1
DC reactor (FR-HEL)
Remove the jumper for the
Main circuit terminal
01160 or less if a DC reactor
is connected. The DC reactor
Control circuit terminal
supplied with the 01800 or
more should be connected to
these terminals.
3-phase AC
power supply
To supply power to the
*2
control circuit separately,
remove the jumper across R1/
L11 and S1/L21.
Control input signals (No voltage input allowed)
Terminal functions vary with the
input terminal assignment set in
Pr. 178 to Pr. 189.
Multi-speed
selection
*3 JOG terminal can be used
as pulse train input
terminal. Use Pr. 291 to
select JOG/pulse.
Second function selection
*4 AU terminal
can be used
as PTC input
terminal.
Current input selection
Selection of automatic restart after
instantaneous power failure
Contact input common (sink*)
24V DC power supply/
max. 100mA load current
Contact input common (source*)
*(Common for external power supply transistor)
Frequency setting signal (analog)
Frequency setting
potentiometer
Ω
1/2W, 1k
*5 Terminal input specifications
can be changed by analog
input specifications switchover
(Pr. 73, Pr. 267).
Set the voltage/current input
switch in the OFF position to
select voltage input (0 to 5V/
Terminal 4
0 to 10V) and ON to select
current input (0/4 to 20mA).
It is recommended to use 2W1kΩ
*6
when the frequency setting signal is
changed frequently.
Fig. 3-3: Terminal connection diagram of the inverter
FR-A700 EC
Earth
Jumper
*2
Earth
Forward
rotation
start
Reverse
rotation
start
Start self-
holding
selection
High speed
Middle speed
Low speed
Jog mode
Output stop
Reset
Auxiliary
input
input
(Current
input)
Connector
for plug-in option
connection
Brake unit
(Option)
Jumper
Jumper
EMC filter
ON/OFF
connector
Main circuit
Control circuit
PU
connector
USB
connector
0–5V DC
0 to 10V DC
4 to 20mA DC
0–±10V DC
0 to ±5V DC
4–20mA DC
0 to 5V DC
0 to 10V DC
Option connector 1
Option connector 2
Option connector 3
Terminating
resistor
Terminal connection diagram
*7 The CN8 connector is provided with the
02160 or more
*8 Brake resistor (FR-ABR)
Remove the jumper across terminal PR-PX
when connecting a brake resistor.
(00023 to 00250)
Terminal PR is provided for the 00023 to
00620.
Install a thermal relay to prevent an overheat
and burnout of the brake resistor.
M
3~
Terminal functions
vary with the input
Relay output 1
terminal assignment
(Alarm output)
set in Pr. 195 and
Pr. 196.
Relay output 2
Running
Terminal functions vary
with the input terminal
Up to frequency
assignment set in
Pr. 190 to Pr. 194.
Instantaneous
power failure
Overload
Frequency detection
Open collector output common
Sink/source common
Analog current output
(0 to 20mA DC)
Analog signal output
(0 to 10V DC)
RS-485 terminals
Data transmission
Data reception
(Permissible load
current 100 mA)
Motor
I001436E
3 - 5