Wiring
3.4.2

Control circuit terminals

Fig. 3-17: Übersicht der Klemmenbelegung
3.4.3

Wiring method

Remove about 6mm of the cable insulation. Wire the stripped cable after twisting it to prevent
it from becoming loose. In addition, do
Loosen the terminal screw and insert the cable into the terminal.
Tab. 3-9: Connection to the terminals
b
CAUTION:
Under tightening can cause cable disconnection or malfunction. Over tightening can
cause a short circuit or malfunction due to damage to the screw or unit.
FR-A700 EC
6mm
Item
Screw size
Tightening torque
Cable size
Screwdriver
.
not solder it
Fig. 3-18:
Preparation of the cable
Description
M3
0,5Nm–0,6Nm
0,3mm²–0,75mm²
Flat blade screw driver
Edge thickness: 0,4mm × 2,5mm
Control circuit specifications
I001018E
I001326E
3 - 27