Advertisement

Position control by vector control
6.5.5

Setting of positioning adjustment parameter (Pr. 426, Pr. 427)

Pr.
Name
No.
426
In-position width
427
Excessive level error
The above parameters can be set when the FR-A7AP (option) is mounted.
When the operation panel (FR-DU07) is used, the maximum setting is 9999. When a
parameter unit is used, up to the maximum value within the setting range can be set.
In-position width (Pr. 426 )
The Y36 signal acts as an in-position signal.
When the number of droop pulses has fallen below the setting value, the in-position signal (Y36)
turns on. For the Y36 signal, assign the function by setting "36" (source logic) or "136" (sink logic)
in any of Pr. 190 to Pr. 196 "Output terminal function selection".
Excessive level error (Pr. 427)
When droop pulses exceed the value set in Pr. 427, position error large occurs and displays an
error (E.OD) to stop the inverter. When you decreased the Pr. 422 "Position loop gain setting",
increase the error excessive level setting. Also decrease the setting when you want to detect an
error slightly earlier under large load.
When "9999" is set in Pr. 427, position error large (E.OD) does not occur regardless of droop
pulses.
6 - 140
Initial
Setting Range
Value
0–32767
100 pulses
pulses
0–400 × 10
3
3
40 × 10
9999
Description
When the number of droop pulses
has fallen below the setting value,
the in-position signal (Y36) turns
on.
A position error excessive (E.OD)
occurs when the number of droop
pulses exceeds the setting.
Function invalid
Parameter
Vector
Vector
Vector
Parameters referred to
Refer to
Section