Function assignment of external terminals
3-wire type (terminals STF, STR and STOP)
A three-wire type connection is shown below.
The start self-holding selection becomes valid when the STOP signal is turned on. In this case,
the forward/reverse rotation signal functions only as a start signal.
If the start signal (STF or STR) is turned on and then off, the start signal is held and makes a start.
When changing the direction of rotation, turn STR (STF) on once and then off. To stop the
inverter, turning off the STOP signal once decelerates it to a stop.
NOTES
The STOP signal is assigned to the terminal STOP in the initial setting. By setting "25" in
Pr. 178 to Pr. 189, the STOP signal can also be assigned to the other terminal.
When the JOG signal is turned on to enable jog operation, the STOP signal becomes
invalid.
If the MRS signal is turned on to stop the output, the self-holding function is not cancelled.
6 - 296
Inverter
Forward
Stop
rotation start
Reverse
rotation start
ON
ON
ON
Inverter
Start
Stop
Forward/
reverse rotation
ON
ON
ON
ON
ON
Fig. 6-129:
3-wire type connection (Pr. 250 = 9999)
Time
ON
Fig. 6-130:
3-wire type connection (Pr. 250 = 8888)
Time
Parameter
I001150E
I001151E