Parameter
6.11.3
Acceleration and deceleration pattern (Pr. 29, Pr. 140 to Pr. 143, Pr. 380 to
Pr. 383, Pr. 516 to Pr. 519)
You can set the acceleration/deceleration pattern suitable for application.
You can also set the backlash measures that stop acceleration/deceleration once at the
parameter-set frequency and time during acceleration/deceleration.
Pr.
Name
No.
Acceleration/deceleration
29
pattern selection
Backlash acceleration
140
stopping frequency
Backlash acceleration
141
stopping time
Backlash deceleration
142
stopping frequency
Backlash deceleration
143
stopping time
380
Acceleration S-pattern 1
381
Deceleration S-pattern 1
382
Acceleration S-pattern 2
383
Deceleration S-pattern 2
S-pattern time at a start
516
of acceleration
S-pattern time at a com-
517
pletion of acceleration
S-pattern time at a start
518
of deceleration
S-pattern time at a com-
519
pletion of deceleration
FR-A700 EC
Initial
Setting
Description
Value
Range
0
Linear acceleration/deceleration
1
S-pattern acceleration/deceleration A
2
S-pattern acceleration/deceleration B
0
3
Backlash measures
4
S-pattern acceleration/deceleration C
5
S-pattern acceleration/deceleration D
1 Hz
0–400 Hz
0.5 s
0–360 s
Set the stopping frequency and time for
backlash measures.
Valid when Pr. 29 = 3
1 Hz
0–400 Hz
0.5 s
0–360 s
Valid when S-pattern acceleration/
0
0–50 %
deceleration C (Pr. 29 = 4) is set.
Set the time taken for S-pattern from star-
0
0–50 %
ting of acceleration/deceleration to linear
acceleration as % to the acceleration/
0
0–50 %
deceleration time (Pr. 7, Pr. 8 etc.).
An acceleration/deceleration pattern can
0
0–50 %
be changed with the X20 signal.
0.1 s
0.1–2.5 s
Valid when S-pattern acceleration/
0.1 s
0.1–2.5 s
deceleration D (Pr. 29 = 5) is set.
Set the time taken for S-pattern accelera-
0.1 s
0.1–2.5 s
tion/deceleration (S-pattern operation).
0.1 s
0.1–2.5 s
Acceleration and deceleration
Refer to
Parameters referred to
Section
3
Base frequency
6.9.1
7
Acceleration time
6.11.1
8
Deceleration time
6.11.1
20
Acceleration/
6.11.1
deceleration ref-
erence frequency
178–189
Input terminal
6.14.1
function selection