Set V/f pattern
Adjustment of elevator mode (Pr. 61, Pr. 64)
By setting the adjustment parameters Pr. 61 and Pr. 64, the application range can be made
wider.
Pr. No.
61
64
Tab. 6-39: Adjustment of elevator mode
NOTES
Even if automatic acceleration/deceleration has been selected, inputting the jog signal (jog
operation), RT signal (second function selection) or X9 signal (third function selection) dur-
ing an inverter stop will switch to the normal operation and give priority to jog operation or
second and third function selection. Note that JOG and RT signal input is invalid even if JOG
signal and RT signal are input during operation with acceleration/deceleration selected.
Elevator mode is invalid when advanced magnetic flux vector, real sensorless vector control
or vector control is selected.
Since the Pr. 61 and Pr. 64 settings automatically return to the initial value (9999) if the
Pr. 292 setting is changed, set Pr. 292 first when you need to set Pr. 61 and Pr. 64.
6 - 180
Name
01800
or less
01800
Reference current
or more
Starting frequency for
elevator mode
Setting Range
Desciption
For example, when the motor and inverter are differ-
0–50A
ent in capacity, set the rated motor current value. Set
reference current (A) of the stall prevention operation
0–3600A
level
The rated inverter output current is defined as refer-
9999
(initial value)
ence.
0–10Hz
Set the starting frequency for the elevator mode.
9999
Starting frequency 2Hz
(initial value)
Parameter