Mitsubishi Electric FR-A700 Instruction Manual page 515

Frequency inverter
Hide thumbs Also See for FR-A700:
Table of Contents

Advertisement

Parameter
NOTES
If it is not possible to adjust the signal to be used for calibration to its maximum value you
can set Pr. 54 to "21". This outputs a continuous signal of approx. 20mA to terminal CA,
which makes it possible to calibrate the maximum value on the meter. When C0 is used to
calibrate the full meter deflection in this mode a value of "1000" is shown on the operating
panel display. Afterwards you can then reset Pr. 54 to the required monitor signal setting.
Current is also output to terminal CA when the parameters are configured as follows:
C8 (Pr. 930) ≥ C10 (Pr. 931) and C9 (Pr. 930) ≥ C11 (Pr. 931).
AM terminal calibration [C1 (Pr. 901)]
Terminal AM is factory-set to provide a 10V DC output in the full-scale status of the correspond-
ing monitor item. Calibration parameter C1 (Pr. 901) allows the output voltage ratios (gains) to
be adjusted according to the meter scale. Note that the maximum output voltage is 10V DC, the
maximum output current 1mA.
AM terminal calibration procedure:
Connect an 0 to 10V DC voltmeter to inverter terminals AM and 5, taking care to correct
with the correct polarity. AM is positive.
Set Pr. 158 to select the monitor signal you want to output to analog output AM (refer to
page 6-330). To display the output frequency or the output current set Pr. 55 or Pr. 56,
respectively, to the maximum frequency or current value for which you want to output 10V
to the terminal.
Start the frequency inverter in PU mode with the operation panel or the control terminals
(external operation).
Calibrate the full deflection of the meter by setting C1 (Pr. 901) and then operating the digital
dial. Note that the value shown on the operating panel for the monitor signal associated with
C1 does not change when you turn the digital dial, but the analog current output to AM will
change as you turn the dial. Confirm the calibration value found by pressing the SET key
(this assigns the maximum voltage output to the displayed value of the monitor signal.)
NOTE
If it is not possible output the signal to be measured for calibration at its maximum value you
can set Pr. 158 to "21". This outputs a continuous signal of approx. 10V to terminal AM,
which makes it possible to calibrate the maximum value on the meter. When C1 is used to
calibrate the full meter deflection in this mode a value of "1000" is displayed. Afterwards you
can then reset Pr. 158 to the required monitor signal setting.
FR-A700 EC
Monitor display and monitor output signals
Fig. 6-153:
Connecting an analog meter to the AM output
10V DC
I001168C
6 - 335