FusionModule2000 Smart Modular Data Center
Maintenance Guide
Table 4-7 Quarterly maintenance for the management system
Item
Battery
management
parameter setting
Fire control
linkage function
Check the
connection of the
iBAT (BIM).
Check the
connection of
iBOX (CIM).
Issue 05 (2020-03-25)
Operation
Check that the
battery
management
parameters in
UPS LCD are
set based on site
requirements.
Simulate a
smoky
environment
under a smoke
detector or
multi-functional
sensor. (If real
smoke is not
allowed, press
the TEST button
on the sensor.)
Check whether
the iBAT (BIM)
is attached
firmly and
whether all
cables are
securely
connected.
Check whether
the iBOX (CIM)
is attached
firmly and all
cables securely
connected.
Copyright © Huawei Technologies Co., Ltd.
Standard
Parameters are set
based on site
requirements.
A smoke alarm is
displayed on the
active alarm page of
the WebUI.
The skylight is
opened.
The alarm beacon
produces audible
and visual alarms.
The iBAT (BIM) is
attached firmly.
All iBAT (BIM)
cables are securely
connected.
No iBAT (BIM)
cable deteriorates
and the insulation
layer does not crack.
The iBOX (CIM) is
attached firmly.
The cable to the
PoE port is
connected securely.
If a cable connects
to the COM port,
check that the cable
connection is
secure.
If a cable connects
to the BCB port,
check that the cable
connection is
4 Routine Maintenance
Troubleshooting
Set parameters
correctly.
Check whether the
smoke detector or
multi-functional
sensor is faulty.
Check whether the
skylight system is
normal.
If the alarm beacon
produces audible
and visual alarms,
check whether the
alarm beacon is
faulty and whether
the cable connection
is proper.
Secure the iBAT
(BIM) again.
Check that all iBAT
(BIM) cables are
securely connected.
Replace the faulty
cable.
Secure the iBOX
(CIM) again.
Reconnect the cable
to the PoE port.
Reconnect the cable
to the COM port.
Reconnect the cable
to the BCB port.
Reconnect the cable
to the HALL current
monitoring port.
26