FusionModule2000 Smart Modular Data Center
Maintenance Guide
Table 3-10 Semiannual maintenance for the management system
Item
Availability
of the smart
ETH gateway
Availability
of the
UIM20A
expansion
module
Availability
of the rack
environment
unit
Issue 02 (2022-07-30)
Method
On the ECC800-
Pro WebUI,
choose
Monitoring >
System > Smart
ETH Gateway
Group > Smart
ETH Gateway.
On the Running
Info page, view
the
communication
status, PoE port
connection, and
power supply
status.
On the ECC800-
Pro WebUI,
choose
Monitoring >
Cabinet > IT
Cabinet > UIM
Group > UIM1.
On the Running
Info page, check
information such
as
communication
status and
temperature.
On the ECC800-
Pro WebUI,
choose
Monitoring >
Cabinet >
System > Rack
Environment
Unit. On the
Running Info
page, check
information such
as
communication
status and
temperature.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Expected Result
The connection
status and power
supply status of the
PoE port on the
smart ETH gateway
can be queried on
the ECC800-Pro
WebUI.
On the ECC800-Pro
WebUI, you can see
that the UIM20A
expansion module
communicates
properly and the
temperature is
displayed properly.
On the ECC800-Pro
WebUI, you can see
that the rack
environment unit
communicates
properly and the
temperature is
displayed properly.
3 Routine Maintenance
Troubleshooting
If the display is
abnormal, check
whether the
communications
cable is loose or
disconnected. If so,
reconnect the cable.
If not, replace the
smart ETH gateway.
If the display is
abnormal, check
whether the
communications
cable is loose or
disconnected. If so,
reconnect the cable.
If not, replace the
UIM20A expansion
module.
If the display is
abnormal, check
whether the
communications
cable is loose or
disconnected. If so,
reconnect the cable.
If not, replace the
rack environment
unit.
43