Huawei FusionModule2000 Maintenance Manual page 45

Smart modular data center
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Maintenance Guide
Item
Indicators on
the rack
environment
unit
ALM indicator
on the UIM20A
expansion
module
Issue 02 (2022-07-30)
Method
Observe the
PWR, RUN,
and ALM
indicators.
Observe the
ALM indicator
on the
UIM20A
expansion
module.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Expected Result
● If the PWR
indicator is steady
green, the power
input is normal.
● The RUN
indicator blinks at
long intervals,
indicating that
the device is
running properly.
● The ALM
indicator is off.
The ALM indicator is
steady on.
3 Routine Maintenance
Troubleshooting
● If the PWR
indicator is off,
check whether
the
communications
cable is loose or
disconnected or
whether the
smart ETH
gateway is not
energized. If so,
reconnect the
cable. If not,
replace the cable.
● If the RUN
indicator blinks at
short intervals,
check whether
the
communications
cable is loose or
disconnected or
whether the
smart ETH
gateway is not
energized.
● If the ALM
indicator is steady
on, check for
alarms.
If the ALM indicator
is steady on, a fault
alarm is generated
for the UIM20A
expansion module.
Check the cable
connections or
replace the UIM20A
expansion module.
38

Advertisement

Table of Contents
loading

This manual is also suitable for:

V100r022c10

Table of Contents