Huawei FusionModule2000 Maintenance Manual page 106

Smart modular data center
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Maintenance Guide
Figure 5-46 Installing a T/H sensor
Step 6 Set the DIP switch on the T/H sensor.
Table 5-10 DIP switch settings on T/H sensors
Locati
on
Cold
aisle
Hot
aisle
Issue 02 (2022-07-30)
Display Name
Cold aisle 1
temp/humid
Cold aisle 2
temp/humid
Cold aisle 3
temp/humid
Cold aisle 4
temp/humid
Cold aisle 5
temp/humid
Hot aisle 1
temp/humid
Copyright © Huawei Digital Power Technologies Co., Ltd.
Addr
DIP Switch No.
ess
1
2
11
ON
ON
12
OFF
OFF
13
ON
OFF
14
OFF
ON
15
ON
ON
21
ON
OFF
5 Parts Replacement
3
4
5
OFF
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
ON
OFF
ON
OFF
ON
6
OFF
OFF
OFF
OFF
OFF
OFF
99