Huawei FusionModule2000 Maintenance Manual page 38

Smart modular data center
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Maintenance Guide
Item
ECC800-Pro RUN
indicator (green)
Ambient
temperature
detection
Indicators on the
iBOX (CIM) and
iBAT (BIM)
Issue 02 (2022-07-30)
Method
Check the RUN
indicator on the
ECC800-Pro
main control
module.
-
Visual
inspection
Copyright © Huawei Digital Power Technologies Co., Ltd.
Expected Result
The RUN indicator
blinks slowly.
The ambient
temperature of
the smart module
should be lower
than 45°C.
● The RUN
indicator blinks
at long
intervals.
● The ALM
indicator is off.
3 Routine Maintenance
Troubleshooting
● If the RUN
indicator blinks
fast, check
whether the
communications
cable is properly
connected
between the
ECC800-Pro and
the host.
● If the RUN
indicator is off,
rectify any input
power grid fault.
Find the cause of an
abnormal
temperature.
● If the RUN
indicator blinks
at short intervals,
check whether
the
communications
cable is loose or
disconnected. If
so, reconnect the
cable. If not,
replace the cable.
● If the ALM
indicator is
steady on, clear
the alarm by
referring to the
iBattery user
manual.
31