Step 6 Synchronize parallel parameters.
1.
2.
Step 7 Clear the EPO state of each UPS. For details, see
UPS.
Step 8 Tap Paral. Inv. ON on the LCD screen Common Functions. The system transfers
to inverter mode.
Step 9 Connect batteries to the parallel system.
Issue 02 (2022-07-18)
Item
Setting
Parallel ID
Number UPSs in
sequence
(example: 1, 2,
3, 4).
Requisite UPSs
Sets it based on
the actual
number of UPSs.
Redundant
Sets it based on
UPSs
the actual
number of UPSs.
Battery Settings: On the LCD, choose System Info > Settings > Battery
Settings. On the WebUI, choose Monitoring > Battery System > Running
Parameter > Battery Settings.
Table 7-2 Battery Settings
Item
Battery string
sharing
NO TE
The system may generate alarms such as Rack quantity mismatch, Insufficient
redundant racks, and Inter-rack par. cable alarm. The alarms are automatically cleared 1
minute after you connect all parallel cables.
If the Inconsistent parallel param. alarm is generated, choose System Info >
Settings on the LCD and tap Parameter Sync to synchronize parameters
between UPSs in the parallel system.
Check that no alarm is generated for any UPS and perform subsequent
operations. If an alarm is generated, follow the troubleshooting suggestion to
clear the alarm first.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Description
-
– In a parallel system, the two
parameters must be set to the
same values for all UPSs.
– The total number of UPSs in a
parallel system is the sum of
Requisite UPSs and Redundant
UPSs.
Setting
Description
Set this
If the parallel system shares one
parameter as
battery string, set this parameter to
required.
Enable.
If each UPS uses an independent
battery string, set this parameter to
Disable.