Huawei FusionPower6000 Maintenance Manual page 71

Hide thumbs Also See for FusionPower6000:
Table of Contents

Advertisement

FusionPower6000
Maintenance Guide
Step 4 Mark the corresponding port names on the cables and remove the cables.
Step 5 Remove the ATS.
Figure 6-28 Removing an ATS
Step 6 Install the new ATS and reconnect the cables.
Step 7 Reinstall the fuse to reconnect the circuit.
Step 8 Set ATS parameters.
Item
Password
Utilisation
of
generator
DI10-
function
Backlighti
ng
duration
● The settings are factory defaults for the ATS in the FusionPower6000.
● ATS parameters can be adjusted based on customer requirements.
Step 9 Check that the Auto indicator on the ATS is steady on and that the switch is in the
Auto position.
Issue 02 (2022-07-18)
Menu Path
System Configuration >
Password
Type of application >
Utilisation of generator
Device Configuration >
Digital Input > DI10-
function
Device Configuration >
Backlighting duration
Copyright © Huawei Digital Power Technologies Co., Ltd.
6 Component Replacement
Setting
The preset password is 0001. Change
the password after the first login to
prevent unauthorized operations.
Generator in use
Disable
Always On
64

Advertisement

Table of Contents
loading

Table of Contents