FusionPower6000
Maintenance Guide
Step 4 Mark the corresponding port names on the cables and remove the cables.
Step 5 Remove the ATS.
Figure 6-28 Removing an ATS
Step 6 Install the new ATS and reconnect the cables.
Step 7 Reinstall the fuse to reconnect the circuit.
Step 8 Set ATS parameters.
Item
Password
Utilisation
of
generator
DI10-
function
Backlighti
ng
duration
● The settings are factory defaults for the ATS in the FusionPower6000.
● ATS parameters can be adjusted based on customer requirements.
Step 9 Check that the Auto indicator on the ATS is steady on and that the switch is in the
Auto position.
Issue 02 (2022-07-18)
Menu Path
System Configuration >
Password
Type of application >
Utilisation of generator
Device Configuration >
Digital Input > DI10-
function
Device Configuration >
Backlighting duration
Copyright © Huawei Digital Power Technologies Co., Ltd.
6 Component Replacement
Setting
The preset password is 0001. Change
the password after the first login to
prevent unauthorized operations.
Generator in use
Disable
Always On
64