Setting Dry Contact Parameters; Setting Communications Parameters; Starting The Inverter - Huawei FusionPower6000 Maintenance Manual

Hide thumbs Also See for FusionPower6000:
Table of Contents

Advertisement

FusionPower6000
Maintenance Guide
Step 4 If the system has connected to the remote EPO switch, you need to choose
Monitoring > UPS System > Running Parameter > System Settings on the
WebUI and set EPO detection to Enable.
Step 5 View the system running status diagram on the LCD to check that the UPS is
working in bypass mode.
----End

7.7.2.3 Setting Dry Contact Parameters

Step 1 Choose System Info > Settings > Dry Contact Settings, set MUE05A connection
to Enable, and set PDC maintenance breaker [MT] to Enable.
Step 2 Choose System Info > Settings > Dry Contact Settings, set MUS05A DO_1
Action to Close, and set MUS05A DO_1 to Sys maint breaker enable.
----End

7.7.2.4 Setting Communications Parameters

Step 1 Choose System Info. > Settings > Comm. Settings > IP Settings and set IP
address allocation to Automatic (DHCP).
Step 2 Choose System Info. > Settings > Comm. Settings > ModbusTCP Settings and
set ModbusTCP encryption to Enable.
----End

7.7.2.5 Starting the Inverter

UPS System User List
Default User
admin (administrator)
operator (common user)
Issue 02 (2022-07-18)
NO TE
● After you set parameters on the Settings Wizard screen, choose System Info > Settings
> System Settings. Check that Requisite modules and Redundant modules match the
actual values.
● If dry contact signals are connected to the system, choose System Info > Settings > Dry
Contact Set. Check that the connected dry contacts have been enabled and that the
disconnected dry contacts have been disabled.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Preset Password
LCD
Web
LCD
Web
000001
Changeme
000001
Changeme
7 FAQ
84

Advertisement

Table of Contents
loading

Table of Contents