7.9.3 Setting a Compensation Cabinet SPD Fault Alarm

Step 1 Choose System Settings > Signal Name Modify. The Batch Signal
Configuration page is displayed.
Step 2 Set Device type and Device name for the ECC800 and click OK
Step 3 On the Query Results tab page, set the signal name of AI/DI_1 to Compensation
Cabinet SPD Fault and click Submit.
Step 4 Choose Monitoring > System > ECC800 > Running Parameters > AI/DI_1 Port
Settings.
Step 5 Set Compensation Cabinet SPD Fault sensor to Enable and click Submit.
Step 6 Set Compensation Cabinet SPD Fault sensor type to Normal close and click
Submit.
Step 7 Choose System Settings > Alarm Parameters, select ECC800 from the Select a
device type drop-down list box, select System-Device name from the Device
Name drop-down list box, and click Confirm.
Step 8 Set Enable Alarm to Enable for Compensation Cabinet SPD Fault DI alarm, and
retain Disable for other alarms related to compensation cabinet SPD faults. Set
Severity to Critical (recommended), Major, Minor, or Warning.
----End

7.9.4 Creating a FusionPower6000 Plan View

To create a FusionPower6000 plan view, it is recommended that you obtain or
draw the planned layout of the FusionPower6000 equipment room first. All
devices are connected and added, and the communication is normal.
Step 1 Choose Home > Plan View and click Create a view in Power Module View. The
Modify Basic Config dialog box is displayed. Set the layout and device quantity in
Location, Layout, and Half-size cabinet qty./row based on the actual
FusionPower6000 scenario.
Figure 7-21 Modifying basic configurations
Step 2 Lay out the FusionPower6000 plan view.