Routine Maintenance; Monthly Maintenance - Huawei FusionPower6000 Maintenance Manual

Hide thumbs Also See for FusionPower6000:
Table of Contents

Advertisement

FusionPower6000
Maintenance Guide

4.1 Monthly Maintenance

Item
Method
Operating
Check the
environmen
operating
t
environment.
Transformer
Check the
temperature
controller.
Check the noise
generated during
device running.
Check the
enclosure.
Issue 02 (2022-07-18)
4
Expected Result
● Ambient temperature: 0°C
to 40°C; humidity: 5% RH to
95% RH (non-condensing)
● Rodent-proof measures have
been taken for the
equipment room.
● The equipment room is
airtight.
The temperature displayed on
the temperature controller is
normal.
No abnormal noise is
generated.
There are no obvious collision
marks or looseness on the
enclosure.
Copyright © Huawei Digital Power Technologies Co., Ltd.

Routine Maintenance

Troubleshooting
● If the temperature and
humidity are abnormal,
check the cooling status
of the equipment room.
● Install a rat guard at the
door of the equipment
room.
● Check that the equipment
room is airtight and not in
a direct ventilation
environment.
● Check that the device runs
within the specifications
on the nameplate.
● Check the operating status
of the temperature
controller and handle
alarms.
● Check that the device runs
within the specifications
on the nameplate.
● If abnormal noise is
generated, contact
technical support.
If the enclosure is abnormal,
repair it in a timely manner.
4 Routine Maintenance