Step 4 After configuring the parameters, click Finish.
Step 5 After confirming that the commissioning Result is normal, enter the Checker
Name and Check Date, and click Configuration Completed.
Step 6 Choose System Settings > Alarm Parameters, select ECC800 from the Select a
device type drop-down list box, select System-Device name from the Device
Name drop-down list box, and click Confirm.
Step 7 Set Enable Alarm to Enable for Compensation Cabinet SPD Fault DI alarm, and
retain Disable for other alarms related to compensation cabinet SPD faults. Set
Severity to Critical (recommended), Major, Minor, or Warning.
Step 8 Choose Monitoring > Power Distribution, click the corresponding transformer,
and set relevant parameters on the Running Parameters tab page.
Issue 02 (2022-07-18)
Parameter
-
-
-
NO TE
To export the configuration result, click Export Check Result. The export file format is csv.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Setting
1. Click One-Click Layout. The Set
One Click Layout Type dialog box
is displayed. Select Left to
right(transformer on the left) or
Right to left(transformer on the
right) based on the actual
scenario of the FusionPower6000.
Set the parameter based on the
actual situation.
2. Drag the icons of registered
devices and devices on the cabinet
list to the corresponding positions
in the layout diagram. Click a
device icon. On the displayed
Basic Configuration page, modify
the value of Device Name and
Device No.. Click Exit Edit Mode
to create a FusionPower6000 plan
view.
3. If the ATS mounting relationship is
inconsistent with the actual
situation, click the cabinet to
which the ATS is to be mounted.
In the displayed dialog box, select
ATS in cabinet and click Finish.
Skip
Skip