Checking The Refrigerant - Huawei FusionCol8000-E24 User Manual

Modular indirect evaporative cooling system
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Figure 5-5 Securing the unit
(1) Maintenance door
Step 5 Hoist the other unit.
Step 6 Place it on the top of the installed unit (ensure that the contact surface is clean).
Step 7 Secure the units at the upper and lower layers.
Step 8 Close the maintenance door after the units are secured.
----End

5.4.3 Checking the Refrigerant

Procedure
Step 1 Open the maintenance door to the compressors.
Step 2 Check whether any needle valve bonnet of the compressors is missing.
1.
2.
Issue 03 (2021-04-20)
If any bonnet is missing, contact Huawei technical support.
If no bonnet is missing, remove the valve bonnets, and press the valve plugs
using the valve bonnets in turn. If gas flows out, the system is normal. If no
gas flows out, contact Huawei technical support.
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 System Installation (FDC Scenario)
76