Symptom
The water
system cannot
spray properly.
Issue 03 (2021-04-20)
Possible Cause
The water pump is sealed by
gas.
NO TE
If the fault persists, contact technical support.
Copyright © Huawei Digital Power Technologies Co., Ltd.
10 Troubleshooting
Solution
When the water pump of the
smart cooling product runs
for the first time every year,
the water pump may be
sealed by gas and cannot
spray properly. In this case,
you need to manually
exhaust air. When the water
pump is running, remove the
exhaust plug on the water
pump. When water flows out
of the exhaust hole, reinstall
and tighten the exhaust plug.
150