FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual

3.2 Operating Environment Specifications

Environmental Specifications
Table 3-5 Environmental specifications
Item
Operating
temperature
Operating humidity
Storage temperature
Storage humidity
Altitude
Table 3-6 Derating coefficients
Altitude
(m)
Air volume
coefficient
Cooling
capacity
coefficient
Installation Requirements
If the total actual load of servers for each equipment is less than 10% of the rated
cooling capacity or the equipment room is not properly sealed, the humidity in the
equipment room may exceed the upper limit, which is not a product quality issue
and should be dealt with by adding a dehumidifier.
Issue 03 (2021-04-20)
1000
1500
0.887
0.835
0.887
0.835
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
Specifications
–40°C to +45°C
5%–95% RH
–40°C to +70°C
5%–95% RH
The performance is not derated when the altitude is
below 1000 m, and is derated when the altitude ranges
from 1000 m to 4000 m.
2000
2500
0.785
0.737
0.785
0.737
3 Product Specifications
3000
3500
4000
0.692
0.649
0.608
0.692
0.649
0.608