Huawei FusionCol8000-E24 User Manual page 189

Modular indirect evaporative cooling system
Table of Contents

Advertisement

FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
2.
Figure 12-33 Refrigerant detection
Table 12-1 Mapping between temperatures and R410A saturation pressures
Temperatur
e (ºC)
0
1
2
3
4
5
6
7
8
9
10
11
12
Issue 03 (2021-04-20)
As shown in
Figure
12-33, place the refrigerant in an indoor place with
constant temperature and humidity for 24 hours. Then, use a thermometer to
measure the temperature of the refrigerant tank outer surface and connect a
pressure gauge to the pressure tank to measure the internal pressure. Find the
saturation pressure corresponding to the measured outer surface temperature
from
Table
12-1. If the deviation between the saturation pressure and the
measured internal pressure is greater than 0.2 MPa, the refrigerant does not
meet the requirements and needs to be replaced.
Saturation
Pressure –
Gauge
Pressure
(MPa)
0.7
0.73
0.75
0.78
0.81
0.84
0.87
0.9
0.93
0.96
0.99
1.02
1.05
Copyright © Huawei Digital Power Technologies Co., Ltd.
Temperatu
Saturation
re (ºC)
Pressure –
Gauge
Pressure
(MPa)
19
1.31
20
1.35
21
1.39
22
1.43
23
1.47
24
1.51
25
1.56
26
1.60
27
1.65
28
1.69
29
1.74
30
1.79
31
1.84
12 Component Replacement
Temperatu
Saturatio
re (ºC)
n
Pressure –
Gauge
Pressure
(MPa)
38
2.21
39
2.27
40
2.33
41
2.39
42
2.45
43
2.51
44
2.57
45
2.63
46
2.7
47
2.76
48
2.83
49
2.9
50
2.97
180