FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Context
The parameters in this section are for reference only. Set practical parameter
values as required.
Procedure
Step 1 On the home screen, tap
Settings screen.
Figure 7-4 Teamwork Settings
Step 2 Set teamwork parameters.
All teamwork control parameters can be set on the master unit. Only Teamwork
group No., System address, Enable teamwork CAN resistor, Teamwork
function, and Networking mode can be set on slave units. Other parameters of
the slave units will be modified by the master unit synchronously.
Parameter
Teamwork group No.
System address
Networking mode
Issue 03 (2021-04-20)
System address: The address (configurable range: 1–32) of each unit in the
same group must be unique. The unit with the smallest unit address is the
master unit, which collects, processes, and delivers group data.
Copyright © Huawei Digital Power Technologies Co., Ltd.
> Teamwork Settings to enter the Teamwork
Description
Specifies the planned teamwork group number. This
parameter should be the same for all units in the
same teamwork group.
Specifies the planned teamwork group number. This
parameter should be the same for all units in the
same teamwork group.
Specifies the networking mode for teamwork control.
The networking mode selected on the screen must
match the actual networking mode. Otherwise, the
teamwork function is unavailable.
7 Power-On Commissioning