Step 8 Power on the unit and tap Start on the home screen. Ensure that the unit is
running normally without any alarms.
----End
12.10 Replacing an Air Exhaust NTC Temperature
Sensor (FDC Scenario)
Prerequisites
●
●
●
Procedure
Step 1 On the home screen of the display module, tap Shutdown and turn off the unit
switch in the PDF.
Exercise caution because the unit is still energized after it is shut down on the
home screen of the display module.
Step 2 Open the maintenance door.
Step 3 Cut off the cable ties and remove the screws that secure the NTC temperature
sensor.
Step 4 Remove the interconnection terminal from the cable of the NTC temperature
sensor.
Step 5 Install the new NTC temperature sensor, reconnect the cables, and secure the NTC
temperature sensor in the original position.
Step 6 Bind the cable ties.
Step 7 Power on the unit and tap Start on the home screen. Ensure that the unit is
running normally without any alarms.
----End
12.11 Replacing an Air Supply NTC Temperature Sensor
Prerequisites
●
●
Issue 03 (2021-04-20)
An NTC temperature sensor needs to be replaced.
A spare NTC temperature sensor of the same model is available and
functional.
Tool: Phillips screwdriver
NO TICE
An NTC temperature sensor needs to be replaced.
A spare NTC temperature sensor of the same model is available and
functional.