FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
Item
Air filter level on
the outdoor air
intake side (EN
779)
Fan type
Air volume
Net weight
Operating weight
1
Test conditions: The outdoor dry and wet bulb temperatures are 35°C and 27°C
respectively; the indoor return and supply air temperatures are 38°C at 25% RH
and 25°C at 50% RH respectively; the external residual pressures of the indoor
and outdoor units are 150 Pa and 100 Pa respectively. If the indoor return air
temperature is lower than 38°C, the cooling capacity of the equipment is
derated.
Table 3-2 Compressor cooling specifications
Item
Compressor type
Number of compressors
Throttling device
Refrigerant
3.1.2 System Specifications (FDC Scenario)
Table 3-3 System specifications
Item
Maximum power
Maximum
current
Total cooling
capacity
Sensible cooling
capacity
Issue 03 (2021-04-20)
Building Scenario
G3
EC
Indoor: 55,000 m
Outdoor: 50,000 m
5000 kg
5500 kg
FDC Scenario
78.5 kW (default power)
140 A (default current)
240 kW
240 kW
Copyright © Huawei Digital Power Technologies Co., Ltd.
3
/h
3
/h
Specifications
Variable-frequency scroll compressor
3
Electronic expansion valve (EEV)
R410A
1
1
3 Product Specifications
29