FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
12.12 Replacing an Air Supply Fan
Prerequisites
●
●
●
Procedure
Step 1 On the home screen of the display module, tap Shutdown and turn off the unit
switch in the PDF.
Exercise caution because the unit is still energized after it is shut down on the
home screen of the display module.
Step 2 Open the maintenance door to the air supply fan and remove the water baffle
plate.
Step 3 If you need to replace the fifth air supply fan, remove the maintenance door
frame, post, and water pipe in front of the fan.
Figure 12-18 Removing the maintenance door frame
Issue 03 (2021-04-20)
A fan needs to be replaced.
A spare fan of the same model is available and functional.
Tools: protective gloves, Phillips screwdriver, diagonal pliers, cable tie
NO TICE
NO TE
Step
3
is not required for replacing other fans.
Copyright © Huawei Digital Power Technologies Co., Ltd.
12 Component Replacement
168